Endpoint:
flammable solids
Data waiving:
study scientifically not necessary / other information available
Justification for data waiving:
other:
Cross-referenceopen allclose all
Reason / purpose for cross-reference:
data waiving: supporting information
Reference
Endpoint:
flash point, other
Type of information:
experimental study
Adequacy of study:
key study
Study period:
12 Oct - 18 Oct 2016
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
guideline study
Qualifier:
according to guideline
Guideline:
EU Method A.9 (Flash-Point)
Deviations:
no
Qualifier:
according to guideline
Guideline:
other: ASTM D7094
Deviations:
no
GLP compliance:
yes
Type of method:
closed cup
Flash point apparatus:
other: Eraflash flash-point tester
Specific details on test material used for the study:
SOURCE OF TEST MATERIAL
- Source and lot/batch No.of test material: Lot # 20003, unit 0022
- Physical state: Clear colourless liquid
- Analytical purity: 99.7%
- Expiration date of the lot/batch: 30 March 2018

STABILITY AND STORAGE CONDITIONS OF TEST MATERIAL
- Storage condition of test material: at room temperature
Key result
Remarks on result:
no flash point up to 100°C

No flash-point was observed below 111 °C, the temperature at which the test item shows significant evaporation.

Interpretation of results:
GHS criteria not met
Conclusions:
Novec 7700 has no flash point up to 111 °C according to EU Method A.9.
Executive summary:

The flash point of Novec 7700 was tested using a closed-cup method. Starting at 25 °C, an attempt was made to ignite the vapour of the test substance for every 2 °C temperature rise. No flash was observed below 111 °C, at which temperature the test item showed significant evaporation. The study was conducted in accordance with EU Method A.9 and was GLP compliant; therefore the study is considered reliable without restrictions.

Reason / purpose for cross-reference:
data waiving: supporting information
Reference
Endpoint:
auto-ignition temperature (liquids)
Type of information:
experimental study
Adequacy of study:
key study
Study period:
12 Oct - 18 Oct 2016
Reliability:
1 (reliable without restriction)
Rationale for reliability incl. deficiencies:
guideline study
Qualifier:
according to guideline
Guideline:
EU Method A.15 (Auto-Ignition Temperature (Liquids and Gases))
Deviations:
no
Qualifier:
according to guideline
Guideline:
DIN 51794 (Testing of mineral oil hydrocarbons - Determination of ignition temperature)
Deviations:
no
Qualifier:
according to guideline
Guideline:
IEC 60079-4 (Electrical apparatus for explosive gas atmospheres. Part 4: Method of test for ignition temperature)
Deviations:
no
GLP compliance:
yes
Specific details on test material used for the study:
SOURCE OF TEST MATERIAL
- Source and lot/batch No.of test material: Lot # 20003, unit 0022
- Physical state: Clear colourless liquid
- Analytical purity: 99.7%
- Expiration date of the lot/batch: 30 March 2018

STABILITY AND STORAGE CONDITIONS OF TEST MATERIAL
- Storage condition of test material: at room temperature
Key result
Auto-ignition temperature:
375 °C
Atm. press.:
> 1 019.7 - < 1 020.2 hPa

The lowest temperature at which ignition of the test item occurred was 377 °C. This temperature was rounded down to the nearest multiple of 5 °C giving an auto-ignition temperature of the test item of 375 °C.

Conclusions:
The auto-flammability temperature of Novec 7700 is 375 °C at 1019.7 - 1020.2 hPa as determined by EU Method A.15.
Executive summary:

The auto-flammability temperature of Novec 7700 is 375 °C at 1019.7 - 1020.2 hPa and was tested using an auto-ignition temperature apparatus. The study was conducted in accordance with EU Method A.15 and was GLP compliant; therefore the study is considered reliable without restrictions.