Endpoint:
flash point, other
Type of information:
experimental study
Adequacy of study:
key study
Study period:
12 January 2018 - 30 May 2018
Reliability:
1 (reliable without restriction)

Data source

Reference
Title:
Unnamed
Year:
2018
Report date:
2018

Materials and methods

Test guideline
Qualifier:
according to guideline
Guideline:
EU Method A.9 (Flash-Point)
Deviations:
no
GLP compliance:
yes
Type of method:
equilibrium method closed cup
Flash point apparatus:
Setaflash apparatus

Test material

Constituent 1
Test material form:
semi-solid (amorphous): gel

Results and discussion

Flash point
Key result
Flash point:
> 300 °C
Atm. press.:
ca. 101.3 kPa

Applicant's summary and conclusion

Conclusions:
Flash Point. Greater than 300 °C, using a closed cup equilibrium method designed to be
Executive summary:

An aliquot (2 g for temperatures up to 100 ºC and 4 g for temperatures above 100 ºC) of the

test item was transferred to the sample cup of the Setaflash 30000-0 tester. The sample was

heated and allowed to equilibrate at the set temperature. The test flame was introduced into

the sample cup for approximately 2½ seconds by sliding the cup shutter open. Observations

were made for ignition of the vapor. If no ignition occurred, the temperature was increased

and the test flame re-introduced. This was repeated until the lowest reproducible temperature

at which a flash occurred, using a fresh sample, was determined.

There was an occurrence where a flash occurred at a temperature not consistent with the other

observations. A fresh sample of test item was used and a replicate flash was not observed. It

was unknown why this flash occurred but it may have been for reasons other than solely due

to the test item.