Registration Dossier
Registration Dossier
Diss Factsheets
Use of this information is subject to copyright laws and may require the permission of the owner of the information, as described in the ECHA Legal Notice.
EC number: 824-458-3 | CAS number: 1263679-68-0
- Life Cycle description
- Uses advised against
- Endpoint summary
- Appearance / physical state / colour
- Melting point / freezing point
- Boiling point
- Density
- Particle size distribution (Granulometry)
- Vapour pressure
- Partition coefficient
- Water solubility
- Solubility in organic solvents / fat solubility
- Surface tension
- Flash point
- Auto flammability
- Flammability
- Explosiveness
- Oxidising properties
- Oxidation reduction potential
- Stability in organic solvents and identity of relevant degradation products
- Storage stability and reactivity towards container material
- Stability: thermal, sunlight, metals
- pH
- Dissociation constant
- Viscosity
- Additional physico-chemical information
- Additional physico-chemical properties of nanomaterials
- Nanomaterial agglomeration / aggregation
- Nanomaterial crystalline phase
- Nanomaterial crystallite and grain size
- Nanomaterial aspect ratio / shape
- Nanomaterial specific surface area
- Nanomaterial Zeta potential
- Nanomaterial surface chemistry
- Nanomaterial dustiness
- Nanomaterial porosity
- Nanomaterial pour density
- Nanomaterial photocatalytic activity
- Nanomaterial radical formation potential
- Nanomaterial catalytic activity
- Endpoint summary
- Stability
- Biodegradation
- Bioaccumulation
- Transport and distribution
- Environmental data
- Additional information on environmental fate and behaviour
- Ecotoxicological Summary
- Aquatic toxicity
- Endpoint summary
- Short-term toxicity to fish
- Long-term toxicity to fish
- Short-term toxicity to aquatic invertebrates
- Long-term toxicity to aquatic invertebrates
- Toxicity to aquatic algae and cyanobacteria
- Toxicity to aquatic plants other than algae
- Toxicity to microorganisms
- Endocrine disrupter testing in aquatic vertebrates – in vivo
- Toxicity to other aquatic organisms
- Sediment toxicity
- Terrestrial toxicity
- Biological effects monitoring
- Biotransformation and kinetics
- Additional ecotoxological information
- Toxicological Summary
- Toxicokinetics, metabolism and distribution
- Acute Toxicity
- Irritation / corrosion
- Sensitisation
- Repeated dose toxicity
- Genetic toxicity
- Carcinogenicity
- Toxicity to reproduction
- Specific investigations
- Exposure related observations in humans
- Toxic effects on livestock and pets
- Additional toxicological data

Flammability
Administrative data
- Endpoint:
- flammable liquids: obsolete as covered by section 'Flash point'
- Type of information:
- experimental study
- Adequacy of study:
- key study
- Study period:
- August 2019
- Reliability:
- 1 (reliable without restriction)
- Rationale for reliability incl. deficiencies:
- comparable to guideline study
Data source
Reference
- Reference Type:
- study report
- Title:
- Unnamed
- Year:
- 2 019
- Report date:
- 2019
Materials and methods
Test guideline
- Qualifier:
- according to guideline
- Guideline:
- other: ASTM E681
- Deviations:
- no
- Principles of method if other than guideline:
- The test apparatus and procedure were according to ASTM E681-2009 and Appendix B1 to ASHRAE Standard 34-2013. The test vessel was a 12-liter spherical grass flask. The ignition source was a spark from a transformer secondary rated at 15,000V/30mA with 0.4 second spark duration. The electrodes were 1mm, L-shaped tungsten wire with 0.25 inches gap. The ignition source was placed at a height of 1/3 the diameter of the flask from the bottom of the flask. Tests were run at 60°C, with humidity of the air adjusted to 50±1% at 23°C. The absolute humidity of the air used for mixing was 0.0088 grams of water vapor per gram of dry air at 23°C. A stirrer was installed in the flask for vapor mixing. Refrigerant/air mixtures were prepared using partial pressures using a pressure transducer. The tolerance of the refrigerant/air concentration was within 0.1% by volume. Tests were conducted in increments of 1.0vol% or less of the refrigerant/air concentration.
Flame propagation was determined as described in Appendix B1, which is the 90 degree fan criterion. After each test, air was introduced to purge the residual refrigerant vapors, followed by evacuation to below one torr. Figure 1 is a schematic of the basic test vessel.
Flask temperatures were measured and controlled within ±3°C of goal temperatures. - GLP compliance:
- not specified
Test material
- Reference substance name:
- (1Z)-1-chloro-2,3,3-trifluoroprop-1-ene
- EC Number:
- 824-458-3
- Cas Number:
- 1263679-68-0
- Molecular formula:
- C3H2ClF3
- IUPAC Name:
- (1Z)-1-chloro-2,3,3-trifluoroprop-1-ene
- Test material form:
- liquid
Constituent 1
Results and discussion
Any other information on results incl. tables
Experimental Results
Our internal testing on HCFO-1233yd(Z) flammability has shown, by strict adherence to ASHRAE 34, that HCFO-1233yd(Z) is flammable at 60°C in the range from 7 to 14 % by volume. Table 1 gives the HCFO-1233yd(Z) flammability testing results at 60°C using 50% RH air at 23°C.
Refrigerant vol % |
Air vol % |
Angle degree |
Flammable? (Y/N) |
1.0 |
99.0 |
0 |
N |
2.0 |
98.0 |
0 |
N |
3.0 |
97.0 |
0 |
N |
4.0 |
96.0 |
0 |
N |
5.0 |
95.0 |
0 |
N |
6.0 |
94.0 |
60 |
N |
7.0 |
93.0 |
120 |
Y |
12.0 |
88.0 |
150 |
Y |
13.0 |
87.0 |
120 |
Y |
14.0 |
86.0 |
100 |
Y |
15.0 |
85.0 |
30 |
N |
16.0 |
84.0 |
0 |
N |
Applicant's summary and conclusion
- Conclusions:
- The test material may form flammable air/vapour mixtures whilst being used, and therefore it is assigned the risk phrase “EUH018: In use may form flammable/explosive vapour-air mixture”. The substance is not classified as flammable.
- Executive summary:
Flammability of HCFO 1233yd(Z) was determined experimentally, according to ASTM E681-2009 and Appendix B1 to ASHRAE Standard 34-2013. The method utilises changing concentrations to determine flammability. The test results show, by strict adherence to ASHRAE 34, that HCFO-1233yd(Z) is flammable at 60°C in the range from 7 to 14 % by volume. Table 1 gives the HCFO-1233yd(Z) flammability testing results at 60°C using 50% RH air at 23°C.
HCFO 1233yd(Z) may form flammable air/vapour mixtures whilst being used, and therefore it is assigned the risk phrase “EUH018: In use may form flammable/explosive vapour-air mixture”. The substance is not classified as flammable.
Information on Registered Substances comes from registration dossiers which have been assigned a registration number. The assignment of a registration number does however not guarantee that the information in the dossier is correct or that the dossier is compliant with Regulation (EC) No 1907/2006 (the REACH Regulation). This information has not been reviewed or verified by the Agency or any other authority. The content is subject to change without prior notice.